MALSHEJ GHAT PSS

  • The Malshej Ghat Pumped Storage Scheme (PSS) is situated on the river Kalu on the border of Pune & Thane Districts in Western Maharashtra. For the Upper Dam site, the nearest Airport is Pune (145 Km), nearest Rail head is Kalyan (105 Km). For the Lower Dam site, which falls in Thane District, the nearest Airport is Mumbai (165 Km), nearest Rail head is Kalyan (85 Km). The project envisages an installed capacity of 700 MW with two reversible units of 350 MW capacity each.
     
    The Project mainly comprises of following as per draft DPR:
     
    The Upper and Lower Dam (about 2 Km downstream of Upper Dam) both are proposed on river Kalu. The Upper Dam and Lower Dam both are [Roller Compacted Concrete (RCC)] and having O.F. & N.O.F. sections totaling to 2450 m and 682 m length respectively. The max. Heights of both the dams are 37 m and 62 m respectively with ungated spillway (Ogee). The Khubi bund (earthen) 17 m height is separating two reservoirs i.e. Upper reservoir of PSS hydel scheme and reservoir of Pimpalgaon Joge Irrigation project.
     
    The water conductor system consisting of Intake structure (vertical), Control shaft, HRT (350 m) and one inclined pressure shaft (length- 650 m & dia- 6.5 m bifurcating to 4.5 m near Power House) leading to P. H. to feed two nos. of reversible Pump/ Turbine units of 350 MW capacity each. The tail discharge from P. H. is taken through a common   1110 m long Tailrace (dia - 9.0 m) to the lower reservoir with downstream surge shaft, outfall structure (horizontal) at end with trash rack panels.
     
    The underground Power House is consisting of Machine hall & Inlet Valve house, and Transformer hall & d/s Valve house with cavity sizes 120 m X 25 m X 52 m and 76 m X 22 m X 24 m respectively. The Cable and Ventilation tunnel (length- 925 m, D-shape 5 m X 5 m) connecting Machine hall & Transformer hall.  The Main Access tunnel (length- 1370 m, D-shape 7.6 m X 8.5 m) provided from left bank of lower dam to the Service bay of the Power House.
     
    The Project would afford Annual Generation of 1680 MU, while the off-peak requirement of energy for Pumping is  2237 MU annually. As per the draft DPR, the estimated cost of project is ` 2695.26 Crores including IDC & FC ` 298.86 Crs (but excluding Transmission cost ` 130.65 Crs) at May’ 2010 price level. The first year and levelised Conversion Cost of project would be ` 3.41 & ` 2.89 per unit respectively.
  •  SALIENT FEATURES
     
    Sl. No. PARTICULARS UPPER DAM LOWER DAM
    I. LOCATION
     
    1. State
    2. Region
    3. Topo sheet No.
    4. District
    5. Taluka / Village
    6. Latitude
    7. Longitude
    8. River
    9. Nearest Rail Head
    10. 10.Nearest Airport
     
     
    Maharashtra
    WesternMaharshtra
    47 E/15
    Pune
    Junnar / Khubi    
    19° 21' 39" N
    73° 47' 46" E
    Kalu
    Kalyan(100 Km)
    Pune & Mumbai    
     
     
    Maharshtra
    Western Maharshtra
    47 E/15
    Thane
    Murbad / Thitabi
    19° 21' 11" N
    73°  46' 18" E
    Kalu
    Kalyan (85 Km)
    Pune & Mumbai
    II. HYDROLOGY
    1. 90% Dependable Yield
     2.Quantity of water required daily for 8 hours power generation
    3. Maximum usable Storage required for weekly cycle of Operation
     
     
     
    14.78 M m3
      6.05   Mm3
     
    14.9 Mm3                       
     
    27.36 M m3
     -
     
     
     -
    III. RESERVOIR
     
    Catchment Area             
    1. Storage in Mm3
          a. Dead Storage                 
          b. Live Storage         
          c. Gross Storage
    2.  Level in Meters
          a. MDDL
          b. FRL      
          c. MWL
     
     
    10.53 sq. km
     
    3.10 Mm3   
    23.75 Mm3
     
    26.85 Mm3                     
    RL 679.00 m
    RL 686.80 m
    RL 687.70 m                   
     
    26.03 sq. km
     
    2.80 Mm3
    15.56 Mm3
    18.36 Mm3
     
    RL 263.00 m   
    RL 286.00 m
    RL 288.50 m
    IV. DAM & APPURTENANT WORKS
    1. DAM
    a. Type of Dam      
    b. Top of Dam                 
    c. Length of Dam                      
    d. Deepest RBL                        
    e. Deepest Foundation Level
    f. Max. Height
     
    1. SPILLWAY
     
    a. Type                                      
     
    b. Design Flood     
    c. Width of Spillway
    d. Crest of Spillway        
    e.Type of energy              
    dissipation    
     
    3. SLUICES
    a. Number                      
    b. Diameter
     
     
     
    Roller Compacted Concrete
    RL 690.00 m   
    2450 m                 
    RL 656.00 m         
    RL 653.00 m   
    37.00 m
     
     
    Ogee Spillway                         
    (Ungated)    
    106 m3/s                       
    110 m                   
    RL 686.80             
    Stepped spillway   
    with stilling basin  
     
     
    ---
    ---
     
     
     
    Roller Compacted Concrete
    RL 291.00 m
    682 m
    RL 232.00 m
    RL 229.00 m
    62.00 m
     
     
    Ogee Spillway                    (Ungated)                                             
    460 m3/s
    78 m
    RL 286.00
    Stepped spillway
    with stilling basin
     
     
    01 No.
    3.30 m
    V. INTAKE
    a. Type                           
    b. Size        
    c. Trash Rack bays
     
    Vertical- 01 No.    
    3.30 m wide, 11 m high
    12 Nos            
     
    Horizontal- 01 No
    4.5 m wide, 13.30 m high
    02 Nos
    VI. CONTROL SHAFT
     
    a  Size        
    b. Stop logs 
     
    c. Service Gate Opening
     
    10 m diameter      
    1 No.           
    6.30 m wide; 8.0 m high 
    1 no.(Quick closing)         
    6.30 m wide; 8.0 m high
     
    10 m diameter      
    1 No.
    7.1 m wide; 9.0 m high
    1 no.
    7.1 m wide; 9.0 m high
    VII HEAD RACE TUNNEL
    Number
    Length
    Shape
    Diameter
    e. Lining
    f. Inclination
    g. Invert Level
     
    1 no
    350 m
    Circular
    8.0 m
    Concrete
    1 in 11
    RL 636.00 m at intake
    RL 606.00 m at Pressure  Shaft
    VIII Pressure Shaft
    Main Shaft
    a.               Number
    b.               Length
    c.               Shape
    d.               Diameter
    e.        Lining
     
     
    1 no.
    650 m
    Circular
    6.5m bifurcating to 4.5 m near power house
    Steel Lining
    IX POWER HOUSE  
    a. Type                                 
    b. Installed Capacity    
     c. Size
    d. C/L of Unit
    e. Service bay level
    TRANSFORMER HALL
    a.             Type
    b.             Size
     
    c.             No. of transformers (GT)
    d.             Rating of transformers
         
     
    Underground
    2X350 MW
    120 m x 25 mX52 m (Ht above draft tube invert)
    RL 221.00 m
    RL 235.25 m
     
     
    Underground
    76mX22mX24m(Ht above transformer cavern foundation)
    02 Nos
    3X 160 MVA, Single phase
     
    X Cable and  Ventilation Tunnel
    a. Number
    b. Length
    c. Shape
    d. Size
    e. Invert Levels
     
    1 no.
    925 m
    D-shape
    5.0 m (wide) x 5.0 m (high)
    RL 300.0 m at portal
    RL 246.75 m at  both PH and  Transformer Caverns
     
      XI Tailrace TUNNEL
    a.     Number
    b.     Length
    c.   Shape
    d. Diameter
    e. Lining
    f. Invert Level
     
    1 no.
    1110.00 m
    Circular
    9.0 m
    Concrete
    RL 208.00 m at Powerhouse
    RL 242.00 m at Lower Intake
    XII SURGE SHAFT
    a.               Type
    b.               Diameter
    c.               Height
    d.               Invert level
    e.      Min. surge Level
    f.       Max. surge level
     
    Simple surge shaft
    15.00 mts
    138.00 mts
    RL 242 m
    RL 276 m
    RL 298 m
     
       XIII Electro-Mechanical Equipment
    Pump Turbine
    a.Type    
     b. Number
    c. Rated Head, Generation
        Rated head pumping 
    d. Rated discharge      
     
    e. Daily Hrs. of generation              
    f. Daily Hrs. of Pumping
     
    g. Head Variation on Pump
    h. Ratio of Length of Water
        conductor system to design head
    Generator Motor
    a.     Rated Output of generator   
    b.Rated Motor output                                                 
    b.      Rated Voltage
    c.      Rated frequency
    d.     Rated Speed            
     
     
    Reversible Francis Pump Turbine   units
    02
    396 m 
    413 m
    105m3/sec per turbine(Generation mode)
    92m3/sec per turbine(Pumping mode)
    8 Hrs.(No generation on Sunday)
    1.  On Week Days – 7 hrs
    2.  On Sunday – 16.10 hrs
    431 m to 400 m i.e., 31 m
    5.4
     
     
     
    350 MW at P.F = 0.9
    430 MW at P.F = 1
    18 KV
    50 Hz
    333 rpm
    XIV SWITCH YARD 
    a.Type 
    b.Size
    c. Elevation
     d. Switching scheme
     e. Voltage level
     
    Air insulated outdoor
    200 x 200 m
    RL 300.0 m 
      One & half breaker
    400 KV
      XV ANNUAL POWER
    a..Annual generation
    b. Annual Pumping
    c.Conversion loss
     
    1680 MU
    2237 MU
    24.9 %
      XVI  PROJECT COST
    (Price level- March 2010)
    a.Civil works
    b. Electro mechanical works
    c. Preliminary land, Bldgs, Misc
    d. Total cost
    e. IDC & FC 
    f. Total cost (excluding transmission)
    g.Transmission cost        
     
     
    Rs. 1151.26 crores
    Rs. 861.22 Crores
    Rs. 383.92 crores
    Rs. 2396.40 Crores
    Rs. 298.86 Crores
     Rs. 2695.26 Crores
     
    Rs. 130.65 crores
    XVII         CONVERSION COST
    (Excluding pumping cost)
    a.First year 
    b.Levellised                 
     
    Rs. 3.41 per unit
    Rs. 2.89 per unit
     